Description
The module is supplied as a small plastic housing designed to fit into an electrical box. Six flying leads of 18AWG are used to connect the module. It also has a priority interupt facility to give fast response and can be fitted in an electrical box behind the pull station.Features
- Easy to install
- Low current draw
- Designed to meet a wide range of applications
- Addressable
- Eight position dip switch for address setting
- Each module can be addressed from 1 to 126
- Fast response
- For use with the FX-350 Series Fire Alarm Control Panel
- Monitor modules can be wired as a Class A (Style D) or Class B (Style B)
Technical Data
Specifications | |
Normal operating voltage | 16-28 VDC |
Max wiring loop resistance | 40 Ω |
Temperature range | 32°F to 120°F (0°C to 49°C ) |
Humidity | 0% to 95% (no condensing or icing) |
Monitored circuit current consumption | |
Quiescent | 600µA |
Alarm (LED on) | 4.6mA |
End-of-line supervisory resistance | 47KΩ, 0.5W |
Analog levels | |
Open-circuit fault | 4 |
Normal | 16 |
Alarm on switch closure | 64 |