The 5496 is the cost effective solution for powering notification appliances required by the Americans with Disabilities Act (ADA). The 5496 has built-in ANSI cadence pattern, which can upgrade older control panels that lack cadence capability. The Output circuits can be programmed as Notification Appliance Circuits, or as Auxiliary Power (configurable for, constant, resettable,or door holder power).
Features
• UL Listed for 6 amps of notification power
• Power supply’s advanced switch mode design reduces damaging heat and manages power up to 50% more efficiently than other systems
• Built-in synchronization for appliances from AMSECO, Gentex®, Faraday, System Sensor®, and Wheelock®
• 24 VDC filtered output voltage
• Four power-limited notification outputs; 2 Class A or 4 Class B, or 1 Class A and 2 Class B
• NACs are programmable as Notification Appliance Circuits, or as auxiliary power to be used as constant, resettable, or door holder power
• 3 amps per output circuit
• Ground fault detector
• Communicates to the FACP via 4- wire SBUS (wire runs up to 6000 ft)
• AC loss delay option shuts off power to non-essential high-current accessories like magnetic door holders
• Lightweight design adds to ease of installation and reduces shipping costs
• UL 864,1481 & 1971 listed
• ANSI Cadence pattern output capability built-in
Specifications
AC Input: 120 VAC at 2.7 A
Output: 24 VDC at 6 amps
Current:
Standby 40 mA
Alarm 160 mA
Notification/Aux.Power circuits: 4
Output configuration:
- 2 Class A (Style Z)
- 4 Class B (Style Y) (1 Class A & 2
Class B)
Amps per output circuit:
3.0 (6.0 amps total)
Notification circuit output:
20.4 to 27.3 VDC, 3.0 amps each,
4.7k EOL resistor required on each
Class B circuit
Battery charging capacity: 35.0 A