**CALL FOR AVAILABILITY**
Description
The basic IntelliKnight 5700 system can be enhanced by adding modules such as 5860 remote annunciator, 5824 serial/parallel printer interface module (for printing
system reports), and 5496 intelligent power module. 5700 supports SD or SK devices. 5700 also features a powerful built-in dual line fire communicator that allows
for reporting of all system activity to a remote monitoring location.
Features
• Built-in support for up to 50 SK detectors and 50 SK modules creating a total point capacity of 100 points
• Built in support for up to 50 SD devices
• Up to 125 zones and 125 output groups
• Uses standard wire—no shielded or twisted pair required
• Built-in digital communicator
• Central station reporting by point or by zone
• Supports Class B (Style 4) and Class A (Style 6 or 7) configuration for SLC
• Drift compensation
• 13 pre-programmed output cadences (including ANSI-3.41) and 4 programmable outputs
• Notification circuits configurable as 1 Class A (Style Z) or 2 Class B (Style Y), or auxiliary power for resettable,constant, or door holder power
• Built-in synchronization for AMSECO, Gentex®,Faraday, System Sensor® and Wheelock® appliances
• Built-in annunciator with 80-character LCD display
• RS-485 bus provides communication to system accessories
• Upload or download programming, event history
Compatibility
The 5700 signal line circuit (SLC) supports multiple
device types of the same protocol:
• SK
• SD
You cannot mix SD and SK SLC devices on a FACP.